Avocent PM3000 Guia do Utilizador Página 116

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 117
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 115
Appendix D: Replacing the Fuses (For Service Personnel Only)
This product contains replaceable fuses. To avoid serious injury and/or damage to your
Avocent PM PDU, make sure:
The PDU is disconnected from a power source and all connected devices are turned off
before replacing a fuse.
Fuses are replaced with an Avocent approved branch circuit fuse class G time delay type
with 20A 600 VAC rating.
CAUTION: Avocent recommends using the Avocent fuse replacement kit. Avocent is not responsible for any issues
that may occur using any other vendor’s fuse replacement kit.
Fuses are replaced by qualified personnel.
Fuses are denoted with the following markings on the board: FC1-FC2, FC3-FC4, FC5-
FC6, FC7-FC8, FC9-FC10, FC11-FC12, FC13-FC14, FC15-FC16, FC17-FC18, FC19-FC20,
FC21-FC22, FC23-FC24, FC1-FC5, FC2-FC6, FC3-FC7, FC4-FC8 . Refer to Appendix B
for fuse(s) to outlet(s) correlation.
WARNING: There is a risk of explosion if the lithium battery is replaced with an incorrect type. Dispose of used
batteries according to the manufacturer’s instructions.
CAUTION: Double pole/neutral fusing.
108 Avocent PMPDU Installer/User Guide